EasyManuals Logo

RTK UC625 series User Manual

RTK UC625 series
59 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #47 background imageLoading...
Page #47 background image
RTK Series UC625 Annunciator
47
Automatic Acknowledge Timer (Located On SPR Card)
Switches SW6-S1 & SW6-S2 are used to control the integrated timer used to provide automatic
acknowledge after a pre-set delay period.
The timer can be set to operate the automatic acknowledge after 15, 50 or 170 seconds or it can be
disabled as required.
SW6
21 3 4
ON
APPROX TIME SPR CARD
SW6.S1 SW6.S2
15 Seconds ON OFF
50 Seconds OFF ON
170 Seconds ON ON
Disabled OFF OFF
Table 28
Internal Horns Disable (Located On SPR Card)
Switches SW6-S3 & SW6-S4 are used to enable the two integral audibles as required.
SW6
21 3 4
ON
FUNCTION Critical Horn Non Critical Horn
SW6.S3 SW6.S4
Enable ON ON
Disable OFF OFF
Table 29

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RTK UC625 series and is the answer not in the manual?

RTK UC625 series Specifications

General IconGeneral
BrandRTK
ModelUC625 series
CategorySecurity System
LanguageEnglish

Related product manuals