Ruijie RG-NBS3200 Series Switches Hardware Installation and Reference Guide Product Overview
20
Note:
1. Power cord retention clips
2. Three-hole AC power receptacle
3. Protective earthing terminal
The device relies on the separate protective earthing terminal.
The device installation must be permanently grounded.
The device must be intended to be used in a location with equipotential bonding (such as a telecommunication
center, a dedicated computer room, or a restricted access area).
Heat Dissipation
The RG-NBS3200-48GT4XS-P adopts side-to-rear heat dissipation, thereby ensuring normal operation. You must
reserve 10 cm distance space at both sides and the back plane of the cabinet to allow airflow. It is recommended that
you clean the device once every 3 months to avoid dust from blocking vents.
Figure 1-20 Flow Scheme of Heat Dissipation
When you install devices, reserve 1 RU (44.45 cm) distance space between neighbor devices to allow airflow.
LED
LED
Panel Identification
State
Meaning
System status LED
Status
Off
The switch is not receiving power.
Blinking green
( 0.5 Hz)
The switch is running, but is not connected to
Ruijie Cloud.
Blinking green (10
Hz)
The switch is being upgraded or initialized.