MODEL F7317603
14
2.2.Basic Setting & Usage
A. Parameter specification
Function
Indicat
or
Factory
Default
Parameter
Set Range
Instruction
Time of
Day
Random
00:00
23:59
Set the time of day when use “ : ”
flash.
Control
Mode
A-01
A-01
A-01
Down-flow regeneration,
regeneration immediately when the
available volume of treated water
drops to zero (0).
A-03
Intelligent Down-flow regeneration,
regenerate starts when the available
volume of treated water calculated
according parameters drops to zero
(0).
A-11
Up-flow regenerate immediately
when the available volume of treated
water drops to zero (0).
A-13
Intelligent Up-flow regeneration,
regenerate starts when the available
volume of treated water calculated
according parameters drops to zero
(0).
Interval
Backwash
Times
F-00
F-00
020
F-0X means X times no backwash.
Water
Treatment
Capacity
10.00
10.00
099.99
Water treatment capacity in one
circle (m
3
).
Unit Mode
HU-01
HU-01
01, 02, 03
01-m
3
02-gal03-L
Resin
Volume
50L
50L
5500L
The resin volume in tank (L).
Feed
water
hardness
Yd1.2
1.2
0.19.9
Hardness of feed water (mmol/L).
Exchange
Factor
AL.65
0.65
0.300.99
Relate to the raw water hardness.
When hardness is higher, the factor