MODEL: N74A1-63510/N74A3-63610/N74B1-63510B/N74B3-63610B
14
Regenerat
ion Time
02:00
02:00
00:00
23:59
Regeneration time” light on
Resin
Volume
20L
20L
5500L
Resin volume in brine tank (L)
Feed
Water
Hardness
Yd1.2
1.2
0.19.9
Feed water hardness (mmol/L)
Exchange
Factor
AL.65
0.65
0.300.99
Relate to the raw water
hardness. When hardness is
higher, the factor is smaller.
Water
Treatment
Capacity
10m
3
099.99 m
3
Water treatment capacity in one
circle (m
3
)
Backwash
Time
10min.
09959
Backwash time(Minute)
Brine &
Slow
Rinse
Time
60min.
09959
Brine &Slow rinse time(Minute)
Brine Refill
Time
5min.
09959
Brine refill time(Minute)
Fast Rinse
Time
10min.
09959
Fast rinse time(Minute)
Maximum
Interval
Regenerat
ion Days
H-30
30
040
Regenerate on the day even
through the available volume of
treated water does not drop to
zero (0).
Output
Control
Mode
b-01
01
01 or 02
Signal turn on start of
regeneration and shut off end of
regeneration. (refer to P4)
Signal available only intervals of
regeneration cycles and in
service. (refer to P4)