MODEL: N74A1-63510/N74A3-63610/N74B1-63510B/N74B3-63610B
13
2.2.Basic Setting & Usage
A. Parameter specification
Function
Indicator
Factory
Default
Parameter
set range
Instruction
Time of
Day
Rando
m
00:00
23:59
Set the time of day when use
flash.
Control
Mode
A-01
A-01
A-01
Meter DelayedRegenerate on
the day although the available
volume of treated water drops to
zero (0). Regeneration starts at
the regeneration time.
A-02
Meter Immediate: Regenerate
immediately when the available
volume of treated water drops to
zero (0).
A-03
Intelligent Meter Delayed: Meter
Delayed Regeneration type, but
by setting Resin Volume, Feed
Water Hardness, Regeneration
Factor, the controller will
calculate the System Capacity.
A-04
Intelligent Meter Immediate:
Meter Immediately Regeneration
Type, but by setting Resin
Volume, Feed Water Hardness,
Regeneration Factor, the
controller will calculate the
System Capacity.
Service
Day
1-03D
099 days
Only for Time Clock Type,
regeneration by days
Service
Hour
1-20H
099 hours
Only for Time Clock Type,
regeneration by hours