Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
11/68
Safety
2. Safety
2.1 Areas of application
2.1.1 Application
To prevent unintentional application which could injure personnel or damage equipment, the following
must be observed:
The unit must only be used as a liquid refrigeration unit intended for water or brine cooling.
The unit must not be installed in areas where the relative humidity (RH) may exceed 85% (95%
if the motor is made for 100% RH).
The primary side must only be charged with refrigerant R717.
Johnson Controls Denmark further accept no liability of any kind for damage to compressor unit
and plant parts caused by torsional oscillation or the like which is attributable to built-in VSD sol-
utions initiated by the customer after delivery.
The secondary side on the evaporator and condenser is only intended for water or brine as cool-
ing medium. The secondary medium is stated on the P&I diagram. Deviations are only permitted
with a written permission from Johnson Controls Denmark.
Installation of the chiller in potentially explosive atmospheres must only take place if the chiller is
fitted with approved explosion-proof equipment.
The compressor must only be used as a refrigeration compressor and within the operating limits
specified in the manual or in a written agreement with Johnson Controls Denmark.
The compressor must only be used with the number of revolutions per minute, as shown on the
compressor name plate.
The compressor must NOT be used:
To evacuate the refrigeration plant of air and moisture.
To put the refrigeration plant under air pressure in view of a pressure testing.
As an air compressor.