Operating manual - ChillPAC and LP ChillPAC Mk 3
010823 en 2021.06
43/68
Operating instructions
5.3.3 Valve positions during operation, ChillPAC
(water-cooled condenser)
Pos. no.
Designation Position during operation
400
Compressor unit valves
Please see the compressor manual
401 Compressor suction stop valve Open
402
Compressor discharge stop valve Open
45
Stop valve for oil recovery / oil return Open
421 Purging valve
Closed
425 Float valve - expansion
Opens automatically
426 Stop valve - expansion Open
428
Liquid drain valve (R717) Closed
431
Stop valve for oil drainage Open
432
Charge valve (R717) Closed
433 Stop valve for oil recovery Open
436 Stop valve for oil recovery Open
437
Stop valve for oil return Open
442 Double stop valve
One outlet open / one outlet closed
443
Safety relief valve (Closed) Fixed set point
444
Safety relief valve (Closed) Fixed set point
445 Double stop valve
One outlet open / one outlet closed
446
Safety relief valve (Closed) Fixed set point
447
Safety relief valve (Closed) Fixed set point
Table 1: Valve positions during operation, ChillPAC