EasyManua.ls Logo

Saftronics SH6 Series - Start up Instructions; System Set up Prior to Operation

Default Icon
24 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
17
SH6- HEATER CONTROLLER SERIES
FIG 3.6 - SH6 POWER CONNECTIONS
Figure 3.6 shows a typical power connection diagram. The
input terminals R,S and T are supplied with a 3 phase, fused
supply.
The load is connected to U, V and W.
The FAN input requires a 220V aux supply to be connected to
ensure adequate cooling of the stack. Failure to connect a
FAN supply can cause damage to the drive.
The O/T output is on overtemperature interlock, which must be
wired in series with the STOP circuit.
4. START UP INSTRUCTIONS AND CALIBRATION PROCEDURE
Don't apply power to the system yet!!!
NOTE: Before continuing with this procedure make sure that the
connections are in accordance to an approved system diagram
4.1 SYSTEM SET UP PRIOR TO OPERATION

Related product manuals