EasyManuals Logo

SAJ HS2 Series User Manual

SAJ HS2 Series
42 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #36 background imageLoading...
Page #36 background image
HS2/AS2 Series
64
Time-of-use Mode: Battery charging period and discharging period can be set , during
charging period, battery can only be charged, while in discharging period, battery can only
be discharged, the rest of the period, battery will behave as Self-use mode.
6.6 Export Limit Setting
6.6.1 APP setting
There are two methods to control the export limit, the two methods are alternative to each other.
Method 1: Export limitation setting is to control the export electricity to the grid.
Method 2: Generation limit is to control the electricity generated by the inverter.
6.7 Self-test (For Italy)
Italian Standard CEI0-21 requires a self-test function for all inverter that connected to utility
grid. During the self-testing time, inverter will check the reaction time for over frequency,
under frequency, overvoltage and undervoltage. This self-test is to ensure the inverter is able
to disconnect from grid when required. If the self-test fails, the inverter will not able to feed
into the grid.

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the SAJ HS2 Series and is the answer not in the manual?

SAJ HS2 Series Specifications

General IconGeneral
BrandSAJ
ModelHS2 Series
CategoryStorage
LanguageEnglish

Related product manuals