PDS33 Series
- 35 -
Function
Code
Function
Description
Unit
Factory
setting
Modification
Type
Communicati
on Address
FD.10
Water shortage
detect time
0.0s 3600.0s
0.1s
0.0s
FD0A
FD.11
Water shortage
detect
frequency
1.00Hz F0.12
0.01Hz
45.00Hz
FD0B
FD.12
Water shortage
detect current
percentage
0.0% 100.0%
0.1%
40.0%
FD0C
FD.13
Water shortage
restart time
0min 9000min
1min
20min
FD0D
FD.14
MPPT low
limit voltage
250.0V FD.15
220V type275.0V
380V type480.0V
0.1V
480.0V
FD0E
FD.15
MPPT high
limit voltage
FD.14 800.0V
220V type330.0V
380V type580.0V
0.1V
580.0V
FD0F
FD.16
MPPT low
limit of output
frequency
0.0% FD.17
0.1%
20.0%
FD10
FD.17
MPPT low
limit of high
frequency
FD.16 100.0%
0.1%
100.0%
FD11
FD.18
MPPT fast
speed down
rate
0 200
1
20
FD12
FD.19
MPPT fast
speed down
time
0.0s 3600.0s
0.1s
0.5s
FD13
FD.20
MPPT start
disturbance
voltage initial
value
0.1V50.0V
0.1V
20.0V
FD14
FD.21
MPPT given
voltgae
0.0V800.0V
0.1V
/
FD15
FD.22
MPPT enable
voltage
0.0V800.0V
0.1V
/
FD16
FD.23
MPPT open
voltage
0.0V800.0V
0.1V
/
FD17