R5 Series
- 13 -
GFCI Monitoring
Integrated
Grid Monitoring
Integrated
AC Short Circuit Current Protection
Integrated
AC grounding detection
Integrated
DC Surge Protection
Integrated
AC Surge Protection
Integrated
Thermal Protection
Integrated
Anti-island Protection Monitoring
AFD
Interface
AC Connection
Terminal Block
DC Connection
MC4
Human Machine Interface
LED+(Bluetooth/Wi-Fi+APP)
Communication Port
RS232(USB)+RS485(RJ45) +DRM(RJ45)
Communication Mode
Wi-Fi/GPRS/4G(Optional)
General Data
Topology
Transformerless
Consumption at Night [W]
<0.2
Consumption at Standby [W]
6
Operating Temperature Range
-40+60[45°C to 60°C with derating]
Cooling Method
Natural Convection
Ambient Humidity
0-100% Non-condensing
Altitude
4000m(>3000m power derating)
Noise [dBA]
<25
Ingress Protection
IP65
Mounting
Rear Panel
Dimensions [H*W*D][mm]
429*418*177
Weight [kg]
18
Standard Warranty [Year]
5(standard)/10/15/20/25(Optional)
Applicable Standard
CQC NB/T 32004,EN62109-1/2,EN61000-6-1/2/3/4,
EN50438,EN50549,C10/C11,IEC62116,IEC61727,RD1699,
G98,G99,UNE206006,UNE206007-1,CEI0-21,AS/NZS4777.2
Note: 1.The above parameters might be slightly modified according to different grid codes.
2.If you need more information about our product certifications, please contact our sales.