29
P5 Output Terminals
Function
Code
Parameter
Name
Setting Range Default Property
P5-06
FMP output
function selection
0: Running frequency
1: Set frequency
2: Output current
3: Output torque (absolute value)
4: Output power
5: Output voltage
6: HDI input (100.0% corresponds
100.0kHz)
7: AI1
8: AI2
11: Count value
12: Communication setting
13: Motor rotational speed
14: Output current (100.0%
corresponds 1000.0A)
15: Output voltage (100.0%
corresponds 1000.0V)
16: Output torque (actual value)
0
P5-07
AO1 output
function selection
0
P5-09
Maximum FMP
output frequency
0.01kHz ~ 100.00kHz 50.00kHz
P5-10
AO1 o󽗈set
coe󽗋cient
-100.0% ~ +100.0% 0.0%
P5-11 AO1 gain -10.00 ~ +10.00 1.00
P5-17
FMR output delay
time
0.0s ~ 3600.0s 0.0s
P5-18
Relay 1 output
delay time
0.0s ~ 3600.0s 0.0s
P5-19
Relay 2 output
delay time
0.0s ~ 3600.0s 0.0s
6.1 Brief introduction of function code

Related product manuals