P9 Fault and Protection
Function
Code
Parameter
Name
Setting Range Default Property
P9-00
Motor overload protection
selection
0: Disabled
1: Enabled
1 ●
P9-01 Motor overload protection gain 0.20 ~ 10.00 1.00 ●
P9-02
Motor overload warning
coecient
50% ~ 100% 80% ●
P9-03 Overvoltage stall gain 0 ~ 100 0 ●
P9-04
Overvoltage stall protective
voltage
650 ~ 780V 760V ●
P9-05 Overcurrent stall gain 0 ~ 100 20 ●
P9-06
Overcurrent stall protective
current
100% 200% 150% ●
P9-07
Short-circuit to ground upon
power-on
0: Disabled
1: Enabled
1 ●
P9-08 Brake unit action starting voltage 700 ~ 800V 750V ●
P9-09 Fault auto reset times 0 ~ 20 0 ●
P9-10 DO action during fault auto reset 0: Not act 1: Act 0 ●
P9-11 Time interval of fault auto reset 0.1s ~ 100.0s 1.0s ●
P9-12
Input phase loss protection/
contactor energizing
protection selection
Unit's digit: Input
phase loss protection
Ten's digit: Contactor
energizing protection
0: Disabled
1: Enabled
11 ●
P9-13
Output phase loss protection
selection
0: Disabled
1: Enabled
1 ●
6.1 Brief introduction of function code