EasyManua.ls Logo

Sako V780 - Page 45

Sako V780
72 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
39
P9 Fault and Protection
Function
Code
Parameter
Name
Setting Range Default Property
P9-00
Motor overload protection
selection
0: Disabled
1: Enabled
1
P9-01 Motor overload protection gain 0.20 ~ 10.00 1.00
P9-02
Motor overload warning
coe󽗋cient
50% ~ 100% 80%
P9-03 Overvoltage stall gain 0 ~ 100 0
P9-04
Overvoltage stall protective
voltage
650 ~ 780V 760V
P9-05 Overcurrent stall gain 0 ~ 100 20
P9-06
Overcurrent stall protective
current
100% 200% 150%
P9-07
Short-circuit to ground upon
power-on
0: Disabled
1: Enabled
1
P9-08 Brake unit action starting voltage 700 ~ 800V 750V
P9-09 Fault auto reset times 0 ~ 20 0
P9-10 DO action during fault auto reset 0: Not act 1: Act 0
P9-11 Time interval of fault auto reset 0.1s ~ 100.0s 1.0s
P9-12
Input phase loss protection/
contactor energizing
protection selection
Unit's digit: Input
phase loss protection
Ten's digit: Contactor
energizing protection
0: Disabled
1: Enabled
11
P9-13
Output phase loss protection
selection
0: Disabled
1: Enabled
1
6.1 Brief introduction of function code