38
P8 Auxiliary Functions
Function
Code
Parameter
Name
Setting Range Default Property
P8-41
Any current reaching
2 amplitude
0.0% ~ 300.0% (rated motor
current)
0.0% ☆
P8-42 Timing function 0: Disabled 1: Enabled 0 ☆
P8-43
Timing duration
source
0: P8-44
1: AI1
2: AI2
3: Panel potentiometer
(analog input corresponds to
the value of F8-44)
0 ☆
P8-44 Timing duration 0.0Min ~ 6500.0Min 0.0Min ☆
P8-45
AI1 input voltage
lower limit
0.00V ~ P8-46 3.10V ☆
P8-46
AI1 input voltage
upper limit
P8-45 ~ 10.00V 6.80V ☆
P8-47
IGBT temperature
threshold
0℃~ 100℃ 75℃ ☆
P8-49 Wakeup frequency
Dormant frequency (P8-51) ~
maximum frequency (P0-10)
0.00Hz ☆
P8-50 Wakeup delay time 0.0s ~ 6500.0s 0.0s ☆
P8-51 Dormant frequency
0.00Hz ~ wakeup frequency
(P8-49)
0.00Hz ☆
P8-52 Dormant delay time 0.0s ~ 6500.0s 0.0s ☆
P8-53
Current running time
reached
0.0 ~ 6500.0 min 0.0Min ☆
P8-54
Output power
correction coecient
0.00% ~ 200.0% 100.0% ☆
6.1 Brief introduction of function code