PA PID Function
Function
Code
Parameter
Name
Setting Range Default Property
PA-21 PID initial value 0.0% ~ 100.0% 0.0% ☆
PA-22
PID initial value
holding time
0.00 ~ 650.00s 0.00s ☆
PA-23
Maximum
deviation between
two PID outputs in
forward direction
0.00% ~ 100.00% 1.00% ☆
PA-24
Maximum
deviation between
two PID outputs in
reverse direction
0.00% ~ 100.00% 1.00% ☆
PA-25
PID integral
property
Unit's digit (Integral separated)
0: Invalid
1: Valid
Ten's digit (Whether to stop
integral operation when the
output reaches the limit)
0: Continue integral operation
1: Stop integral operation
00 ☆
PA-26
Detection value of
PID feedback loss
0.0%: Not judging feedback loss
0.1%–100.0%
0.0% ☆
PA-27
Detection time of
PID feedback loss
0.0s ~ 20.0s 0.0s ☆
PA-28
PID operation at
stop
0: No PID operation at stop
1: PID operation at stop
0 ☆
6.1 Brief introduction of function code