14 | EN STOUCH v2019.1
F.0 Speed 1 (Pa) 0 – 999 x 10 5
F.08 Speed 2 (Pa) 0 – 999 x 10 10
F.09 Speed 3 (Pa) 0 – 999 x 10 25
F.10 Speed 4 (boost) (Pa) 0 – 999 x 10 40
F.11 Pressure PID – P 0 – 999 5
F.12 Pressure PID – I 0 – 999 10
F.13 Pressure PID – D 0 – 999 0
F.14 Converter
0: No
1: Pressure
2: CO
2
0
F.15 Converter MIN 0 - 250 x 10 0
F.16 Converter MAX 1 - 250 x 10 200
F.1
Controller Modbus master/slave ad-
dress
0: Master
1 - 247: Slave
0
F.18 Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
4
F.19 Setting of data package
0: N,8,1;
1: E,8,1;
2: O,8,1;
3: N,8,2;
4: E,8,2;
5: O,8,2;
1
F.20
Operated device (remote controller au-
tomatically recognizes PRV, EKR, MCB
ir ECO control boards).
0: None
1: Custom
2: ECO
3: PRV
4: MCB
5: EKR
0
F.21 Modbus address of controlled device 1 - 247 1
F.22 SET Temperature address 00:00 - FF:FF 00:00
F.23 SET Fan speed (%) address 00:00 - FF:FF 00:00
F.24 SET Fan speed xed address 00:00 - FF:FF 00:00
F.25 SET Pressure address 00:00 - FF:FF 00:00
F.26 SET CO
2
address 00:00 - FF:FF 00:00
F.2 Temperature address 00:00 - FF:FF 00:00
F.28 Alarm 1 address 00:00 - FF:FF 00:00
F.29 Alarm 2 address 00:00 - FF:FF 00:00