EN | 17STOUCH v2019.1
Speed 2 (Pa) 0 – 999
Holding
register
0x08 8
Speed 3 (Pa) 0 – 999
Holding
register
0x09 9
Speed 4 (boost) (Pa 0 – 999
Holding
register
0x0A 10
Pressure PID – P 0 – 999
Holding
register
0x0B 11
Pressure PID – I 0 – 999
Holding
register
0x0C 12
Pressure PID – D 0 – 999
Holding
register
0x0D 13
Converter
0: No
1: Pressure
2: CO
2
Holding
register
0x0E 14
Converter MIN 0 - 250 x 10
Holding
register
0x0F 15
Converter MAX 1 - 250 x 10
Holding
register
0x10 16
Controller Modbus master/
slave address
0: Master
1 - 247: Slave
Holding
register
0x11 17
Modbus data transfer rate
0: 1200
1: 2400
2: 4800
3: 9600
4: 19200
5: 38400
6: 57600
7: 115200
Holding
register
0x12 18
Setting of data package
0: N,8,1;
1: E,8,1;
2: O,8,1;
3: N,8,2;
4: E,8,2;
5: O,8,2;
Holding
register
0x13 19
Controlled device
0: None
1: Custom
2: ECO
3: PRV
4: MCB
5: EKR
Holding
register
0x14 20
Modbus address of con-
trolled device
1 - 247
Holding
register
0x15 21
SET Temperature address 00:00 - FF:FF
Holding
register
0x16 22
SET Fan speed (%) ad-
dress
00:00 - FF:FF
Holding
register
0x17 23