6. Attach Wiring
Connect the labeled wires to their matching terminals based on the fan coil
configuration as follows:
Configuration
R
C
WY
YA
Gl
Gm
Gh
Ac
Ac
Tp
Tx
Ts
Tc*
2-pipe Heat Only
W
O
O
O
O
O
2-pipe Cool Only
Y
O
O
O
O
O
2-pipe Heat or Cool -
Manual changeover
W/Y
O
O
O
O
O
2-pipe Heat or Cool -
Seasonal changeover
W/Y
O
O
O
O
2-pipe Heat or Cool with
Auxiliary Heat
W/Y
A
O
O
O
O
4-pipe Heat / Cool,
Manual or Auto changeover
W
Y
O
O
O
O
O
: Required O: Optional
* If using more than one T terminal (Tp,Tx,Ts), it may be necessary to splice for Tc.