EasyManua.ls Logo

Samson 2413 Series - Technical Data

Samson 2413 Series
52 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
16 EB 2517 EN
Design and principle of operation
3.1 Technical data
The valve and actuator nameplates provide
information on the valve and actuator ver-
sions(seesection2).
Process medium and scope of application
TheType41-73ExcessPressureValveis
used to maintain the pressure upstream of
the regulator to an adjusted set point.
The regulator is suitable for controlling liq-
uids, gases or vapors up to 350°C.
For liquids, gases or vapors
Max.temperature350°C
Set points from 0.05 to 28bar
ValvesizeDN15 to 100
Pressure ratings from PN16 to 40
The regulator is closed when relieved of
pressure. The valve opens when the up-
stream pressure rises.
Temperature range
Dependingonhowtheregulatoriscong-
ured, it can be used up to temperatures of
350°C(Table1).Theminimumtemperature
is limited by the accessories used and the ac-
tuator's diaphram material (uT2595).
Leakage class
The metal-seated regulator has the leakage
classIaccordingtoIEC60534-4.
The soft-seated regulator has the leakage
classIVaccordingtoIEC60534-4.
Noise emission
SAMSON is unable to make general state-
ments about noise emission as it depends on
the regulator version, plant facilities and
process medium.
Risk of hearing loss or deafness due to loud
noise.
Wear hearing protection when working near
the regulator.
The Type41-73 Excess Pressure Valve is not
a safety valve. If necessary, a suitable over-
pressure protection must be installed on site
in the plant section.
Dimensions and weights
Table5providesasummaryofthedimen-
sions and weights. The lengths and heights
in the dimension diagrams are shown on
page22onwards.
WARNING
!
Note

Related product manuals