EB 8331-4 EN 85
Decommissioning and disassembly
Code
Parameters Setting range (select ESC to cancel) WE Section Customer
data
c35 End position guiding
(stem
retracts)
50.0 to 100.0%
97.0 % 9.4
c36 End position guiding (stem
extends)
0.0 to 49.9%
1.0 % 9.4
c37 Superimposing an error
message
YES (error reading active)
NO (error reading inactive)
NO 9.5
Operation
c42 Direction of action >> (increasing/increasing)
<> (increasing/decreasing)
>> 9.3
c43 Restart NORM (normal)
ZERO (zero calibration)
FIX (xed positioning value)
STOP (stop in manual level)
NORM 9.9
c44 Fixed positioning value for
restart
0.0 to 100.0% 0.0 % 9.9
Blockage
c51 Blockage detection NO (function inactive)
YES (function active)
NO 9.10
c52 Blockage removal NO (function inactive)
YES (function active)
NO 9.10
c53 Blocking protection of valve NO (function inactive)
YES (function active)
NO 9.10
Valve travel
c61 Rated travel
u Read only [mm] 9.11
c62 Gear version
u Read only 9.11
c63 Limited travel range 10.0 to 100.0% 100.0 % 9.11
c64 Speed level NORM (normal), FAST (fast) NORM 9.11
c65 Stroking speed
u Read only [mm/s] 9.11
c66 Transit time
u Read only [s] 9.11
c67 Dead band (switching
range)
0.5 to 5.0% 2.0 % 9.11