2.2.1 Configuration using TROVIS-VIEW software
The positioner can be configured using the TROVIS-VIEW Configuration and Operator Inter-
face software.
The positioner is equipped with an additional digital SERIAL INTERFACE to connect the RS-232
or USB port of the computer to the positioner over an adapter cable.
The TROVIS-VIEW software enables the user to easily set parameters in the positioner and view
process parameters online.
The Mounting and Operating Instructions EB 8384-5 EN contain a description on how to con-
figure and operate the positioner over TROVIS-VIEW.
2.2.2 Configuration using the NI-FBUS™ Configurator
The NI-FBUS™ Configurator from National Instruments can also be used to configure the
positioner. For this purpose, an interface card must be installed in a computer to connect it to the
F
OUNDATION™ fieldbus.
The integrated function blocks can be linked using the NI-FBUS™ Configurator.
2.3 Communication
The positioner is completely controlled over the digital signal transmission implemented accord-
ing to F
OUNDATION™ fieldbus specification.
Data are transmitted as bit-synchronous current modulation at a rate of 31.25 kbit/s over
twisted-pair cables conforming to IEC 61158-2.
Note: In the case, complex functions are started in the positioner, which require a long calcula-
tion time or lead to a large quantity of data being stored in the volatile memory of the
positioner, the alert “busy” is issued over DD.
This alert is notafaultalarmand can simply be confirmed.
10 KH 8384-5 EN
Principle of operation