EasyManua.ls Logo

Samson Series 3730 - User Manual

Samson Series 3730
216 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
Loading...
Translation of original instructions
EB 8384-3 EN
Firmware version 1.61
Edition April 2022
Series3730
Type3730-3 Electropneumatic Positioner
Communication: HART
®
Old design
New design

Table of Contents

Other manuals for Samson Series 3730

Questions and Answers

  • D
    Daniel DuncanAug 11, 2025
    Why is my Samson 3730 actuator moving in the wrong direction?
    • E
      Elizabeth RichardsonAug 11, 2025
      If your Samson Valve Positioner's actuator moves in the wrong direction, first check the characteristic setting. Also, inspect the piping and the configuration of the mounting parts.
  • J
    justinclementsAug 17, 2025
    How to fix slow movement of actuator in Samson Valve Positioners?
    • B
      benjamin77Aug 17, 2025
      If the actuator on your Samson Valve Positioner moves too slowly, you should check the supply pressure. Additionally, consider deactivating any software restrictions. Inspect the cross-section of the piping and screw fittings, and verify the configuration of the mounting parts.
  • D
    Denise CrossAug 23, 2025
    What to do if Samson 3730 Valve Positioners leaks air?
    • A
      Arthur SchmidtAug 23, 2025
      If you notice air leaks from your Samson Valve Positioner, examine the attachment. Also, check the seals in the connecting plate.
  • A
    Anthony HenryAug 29, 2025
    How to troubleshoot a Samson Valve Positioners with no display reading?
    • J
      Jordan PorterAug 29, 2025
      If there is no reading on the display of your Samson Valve Positioner, start by checking the electrical connection and electrical power. Also, check the ambient temperature, making sure it's within the display's operating range of –30 to +65 °C.
  • M
    Mary WarrenSep 4, 2025
    What to do if the actuator stem does not move on demand in my Samson Controller?
    • R
      richard90Sep 4, 2025
      If the actuator stem on your Samson Controller isn't moving, first, check for any blockages. Be careful, as a blocked actuator can suddenly move uncontrollably, potentially causing injury. Disconnect and lock the pneumatic air supply and control signal before attempting to remove any blockage. Release any stored energy in the actuator, such as spring compression. Also, check the signal pressure and the signal pressure line for leaks. Ensure the signal pressure is connected to the correct diaphragm chamber, referring to the 'Installation' chapter. Finally, a defective diaphragm in the actuator could be the cause; in this case, you would need to replace the diaphragm.

Samson Series 3730 Specifications

General IconGeneral
Supply Pressure1.4 to 7 bar (20 to 100 psi)
Ambient Temperature-40 to +80 °C (-40 to +176 °F)
Enclosure RatingNEMA 4X / IP66
Output PressureUp to supply pressure
MountingDirect mounting on linear and rotary actuators