Level of the heating characteristic
Parallel displacement of the heating characteristic deter-
mined by the displacement value upwards (positive
value) or downwards (negative value) (30 to +30 °C )
If you want to change it:
Press the enter key, the displacement arrows
start to blink.
Use the arrow keys to set the required displace-
ment value in °C.
Press the enter key to acknowledge the value.
(
You can only change this setting when the flash adapta-
tion is not activated)
Proceed in the same manner to enter the following parameters!
Max. flow temperature
(20 to 130 °C)
If you set the max. value = min. value, this results in a
fixed value
Min. flow temperature
(20 to 130 °C)
Set-back of flow temperature
for reduced operation
(0 to 50 °C)
See chapter 4.3 on reduced operation
Outdoor temperature limit value for summer time
operation
(0 to 50 °C)
See chapter 4.4 on summer time operation