EB 5573 EN 16-61
Appendix A (conguration instructions)
switched off when either the water temperature measured at sensor SF2 has reached the
'Max.storagetanktemperature'orwhenthesolarcollectortemperaturerisesabove120°C.
The times-of-use of the DHW circuit do not affect the operation of the solar system.
After the key number 1999 has been entered, the operating hours of the solar pump are dis-
played in extended information level.
Parameters Default Parameter level: value range
Solar circuit pump ON 10.0°C PA4:1.0to30.0°C
Solar circuit pump OFF 3.0°C PA4:0.0to30.0°C
Max. storage tank temperature 80.0°C PA4:20.0to90.0°C
16.3.5 Intermediate heating
This function can only be activated in systems Anl 2.x, 4.1 and 4.5.
WiththesettingCO4->F07-1,heatingoperationoftheUP1heatingcircuitisreactivated
for a period of ten minutes after 20 minutes of priority operation (heating deactivated during
DHWheating).BysettingCO4->F07-0,storagetankchargingisgivenunlimitedpriority
over the heating operation in the UP1 heating circuit.
Functions Default Conguration
Intermediate heating 1 CO4->F07-1
16.3.6 Parallel pump operation
This function can only be activated in systems Anl 2.1 to 2.1, 4.1 and 4.5.
WhenCO4->F06-1,thecirculationpumpUP1remainsactivatedduringDHWheating.
Thisdoesnotincludeoperatingsituationsduringwhichthecurrentowtemperaturedemand
of the pump circuit is lower than the adjusted 'Flow temperature limit for parallel operation'.
In this case, the controller applies priority operation, if necessary with intermediate heating.
Once a parallel pump operation cycle has been activated and the time period set in 'Stop
parallel pump operation in the event of a system deviation' has elapsed, system deviations
greaterthan5°Ccausethecontrollertosuspendparalleloperationfor10minutesandto
apply priority operation.
Setting'Stopparallelpumpoperationintheeventofasystemdeviation'to0minleadstoa
parallel operation once initiated remaining regardless of a deviation.