16-80 EB 5573 EN
Appendix A (conguration instructions)
16.6 Function block lists
CO1: Rk1 · Heating circuit 1 (not system Anl1.9)
1)
F Function WE Anl
Comments
Function block parameters: value range (default setting)
01 Room sensor
RF1
0
Not sys-
tems Anl
1.5, 1.6,
3.x, 16.x
CO1->F01-1:TemperaturereadingandFG1inputfor
Type5244and5257-5orType5257-51RoomPanelsactive
02 Outdoor sensor 0
1.5, 1.6
CO1->F02-1:OutdoorsensorAF1
Outdoor-temperature-compensated control active
1
Not Anl
1.5, 1.6
03 Returnow
sensor RüF1
0
1.2
CO1->F03-1:
Sensor and limitation function active
Function block parameters:
KP (limiting factor): 0.1 to 10.0 (1.0)
1
Not Anl
1.2
04 Cooling control 0
All
1)
CO1->F04-1:Coolingcontrol,onlywithCO1->F11-1
The cooling control function causes a reversal of the operating
directionandaminimumlimitationofthereturnowtempera-
ture in Rk1.
05 Underoor
heating
Drying of joint-
lessoors
0
Not sys-
tems Anl
1.5, 1.6,
3.x, 16.x
CO1->F05-1:Restrictionoftheadjustmentranges
Function block parameters:
Boost:0.0to50.0°C(0.0°C)
Starttemperature:20.0to60.0°C(25°C)
Hold (days): 0 to 10 days (0)
Temp.rise/day:0.0to10.0°C(5.0°C)
Maximumtemperature:25.0to60.0°C(45.0°C)
Hold (days): 0 to 10 days (4)
Temp.reduction/day:0.0to10.0°C(0.0°C)
STOP,
START,
START,
START,
START
06 Storage tank
sensor SF2
1 System Anl
16.x only
CO1->F06:ActivateSF2toswitchoffchargingofthebuffer
tank
07 Optimization 0
Not sys-
tems Anl
1.5, 1.6,
3.x, 16.x
CO1->F07-1:onlywhenCO1->F01-1and
CO1->F02-1
08 Adaptation 0
Not sys-
tems Anl
1.5, 1.6,
3.x, 16.x
CO1->F08-1:onlywhenCO1->F01-1,CO1->F02-1