16-92 EB 5573 EN
Appendix A (conguration instructions)
F Function WE Anl
Comments
Function block parameters: value range (default setting)
03 Modem
function
0
All
CO6->F03...F06isrequiredtoconguretheerrormessage
transfertoaconnectedModbus/GPRSgateway(1402-0701).
04 Automatic
modem
conguration
0
All
05 Lock dial-up to
building
automation
system
0
All
06 Dial-up to
building
automation
system also to
indicate that an
error has been
remedied
0
All
07 Monitoring 0
All
CO6->F07-1:Resetallevenbitsto'autonomous'whenthere
isnocommunication(onlywhenCO6->F01-1)
08 Text message 0
All
CO6->F08isrequiredtoconguretheerrormessagetransfer
toaconnectedModbus/GPRSgateway(1402-0701).
20 Modbus
without
building
automation
system
0
All
CO6->F20-1:VariousModbusspecicationsdonothave
anyeffectonthecollectivelevel/buildingautomationsystem
reading
F Function block number, WE Default setting, Anl System code number
CO8: Initialization of BI1 and BI2 (all systems)
F Function WE Anl
Comments
Function block parameters: value range (default setting)
01 Analysis of BI1 0
All
CO8->F01-1:Analysisactive
Function block parameters:
ErrormessagewhenBI=0,BI=1,none(1)
02 Analysis of BI2 0
All
CO8->F02-1:Analysisactive
Function block parameters:
ErrormessagewhenBI=0,BI=1,none(1)