EB 5573 EN 16-93
Appendix A (conguration instructions)
16.7 Parameter lists
PA1: PA1 parameters (heating circuit 1)
PA2: PA2 parameters (heating circuit 2)
Pictogram
Parameter name
Value range (default setting)
Flow gradient
0.2 to 3.2 (1.2)
(whenCO1,2->F05-1,0.2to1.0(0.5)applies)
Level (parallel shift)
–30.0to+30.0°C(0.0°C)
Min.owtemperature
–5.0to+150.0°C(20.0°C)
Max.owtemperature
5.0to150.0°C(70.0°C)
WhenCO1,2->F05-1:5.0to50.0°C(50.0°C)

Related product manuals