EB 5573 EN 8-7
Setup
8.2.5 Programming vacation periods (special times-of-use)
The system runs constantly in reduced mode during vacation periods. A maximum of ten va-
cation periods can be entered. Each vacation period can be separately assigned to the heat-
ingcircuitsRK1,RK2and/ortheDHWcircuit.
Parameters Default Level: value range
Vacation period (START, STOP) Extended information level: 01.01 to 31.12
How to proceed:
1. In the extended information level (normal switch posi-
tion
) select the data point for vacations [q].
Reading:
2. Open data point for public holidays [Û].
Reading: START
3. Select – –.– – on the display [q] (if applicable).
4. Activate editing mode for the start date of the vacation
[Û].
and blink.
5. Set the start date of the vacation [q].
6. Conrmthestartdatesetting[Û].
Reading: STOP, – –.– –
7. Set the end date of the vacation [q].
8. Conrmtheenddatesetting[Û].
Black squares at the top of the display indicate the as-
signment of the vacation periods to the individual con-
trol circuits.