14
Installation Procedure
English
Installation Procedure
CAUTION
While on site and prior to installation, protect or enclose
refrigerant tubing to avoid mechanical damage.
Be sure to use hard drawn ACR tubing for all piping
Ø3/4"(19.05mm) or greater. If you use annealed copper
for 3/4" (19.05mm), the pipe may break which can
result in an injury.
After
connecting
the pipes, block
the part .
Make at least one round:
It will reduce noise and vibration
The designs and shape are subject to change according to the model.
(A) Heat radiation holes
Do not block the holes.
Pipe outlet
The refrigerant pipe can be pulled out from front, side,
rear and bottom side, so install it depending on the
installation site condition.
CAUTION
Cut the pipe outlet to the exact pipe size. In addition,
remove foreign substances and burr around the outlet.
Make sure not to damage the exterior of the outdoor
unit.
ťʪθ˙ͱθʀЇϩϩ˝иϩ˵ͱцɇʀЇϩϩʪθ࣍ʪуࢋΧΧʪθ࣎ɇʒ
never tap with a hammer near the pipe outlet.
Otherwise, it may cause product damage such as
warping of the cabinet.
After connecting the pipes with Pipe outlet, plug the
space around the pipes.
After connecting the pipes, proceed exactly as directed
in the guide to prevent interference with the internal
parts.
After installing pipes, block the unused knock outs to
prevent small animals from entering. However, the
radiant heat hole(A) should be able to intake air.
Step 6 Brazing the refrigerant pipe
Important information for refrigerant pipe work
Make sure that there is no moisture inside the pipe.
Make sure that there are no foreign materials and
impurities in the pipe.
Make sure that there is no leak.
Make sure to follow the instruction when brazing and
keeping the pipe.
Nitrogen flushing while brazing
Use dry nitrogen gas when brazing the pipes as shown
in the picture.
If you do not perform nitrogen flushing when brazing
the pipes, oxide may form inside the pipe. It can
cause the damage of the important parts such as
compressor, valves.
Adjust the flow rate of the Nitrogen flushing with a
pressure regulator to maintain 0.03 CFH(0.05/hr) or
less.
Brazing part
עߢࢥߥ࢑࣍ߧࢋߤߦ࣎ʀͱΧΧʪθΧΧʪ
Shut-off
valve
Taping
Flow meter
High pressure hose
Pressure regulator
ki]_TXYW][hTWWptjhjG|GvhhluUGGGX[ YWYYTXWTZXGGG㝘㤸GXWa[_a\^