4. Press the / button to set the installation option code in order. Press button to go to the next page.
SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
0 2 RESERVED
Exterior temperature
sensor
Central control RESERVED
SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
1 RESERVED RESERVED Use of Heater
Controller variables
for auxiliary heater
Master / Slave
SEG13 SEG14 SEG15 SEG16 SEG17 SEG18
2 External control
External control
output
RESERVED Buzzer RESERVED
SEG19 SEG20 SEG21 SEG22 SEG23 -
3
Individual control of a
remote controller
Heating setting
compensation
RESERVED RESERVED -
Option No. : 02XXXX-1XXXXX-2XXXXX-3XXXXX
Option SEG1 SEG2 SEG3 SEG4 SEG5 SEG6
Explanation
PAGE MODE
RESERVED
Use of external
temperature sensor
Use of central control
RESERVED
Indication
and Details
Indication
Details
Indication
Details
Indication
Details
Indication
Details
02
0 Disuse 0 Disuse
1 Use 1 Use
Option SEG7 SEG8 SEG9 SEG10 SEG11 SEG12
Explanation
PAG E
RESERVED RESERVED
Use of Heater
Controller variables for auxiliary
heater
Master / Slave
Indication
and Details
Indication
Details
Indication
Details
Indication
Details Indication Details
1
0 Disuse
Set
temperature
for auxiliary
heat on
Time delay
for auxiliary
heat on
0 slave
1Use
0
No temperature
oset
No delay
1
master
1
No temperature
oset
10 minutes
--
2
Use
(Heater
Time
Delay)
2
No temperature
oset
20 minutes
3 2.7°F (1.5°C) No delay
4 2.7°F (1.5°C) 10 minutes
5 2.7°F (1.5°C) 20 minutes
6 5.4°F (3°C) No delay
7 5.4°F (3°C) 10 minutes
8 5.4°F (3°C) 20 minutes
9 8.1°F (4.5°C) No delay
A 8.1°F (4.5°C) 10 minutes
B 8.1°F (4.5°C) 20 minutes
C 10.8°F (6°C) No delay
D 10.8°F (6°C) 10 minutes
E 10.8°F (6°C) 20 minutes