Installing the air conditioner
Pressure table for temperatures
If you need extra refrigerant charging due to leakage or relocating the product, refer to below table before charging
refrigerant.
Cooling operation
Unit : [kPa, G]
Indoor temperature (°C)
(Dry bulb / Wet bulb)
Outdoor temperature(°C)
32/23 27/19 21/15
52 1110 900 780
35 920 750 640
21 830 690 590
7 690 540 490
-15 550 400 370
Heating operation
Unit : [kPa, G]
Indoor temperature (°C)
(Dry bulb / Wet bulb)
Outdoor temperature(°C)
27/15 20/15 13/10
24 3630 3400 3100
7 2840 2670 2400
-5 2650 2470 2200
-20 2060 1890 1620
Pressure for each temperature was measured at gas side service valve.