Fixing and insulating the connection part of the pipe
Check the leakage on the connection part of pipes and make sure the
insulated them afterwards. Pipe must be insulated properly so that
condensation does not form.
Use foamed polyethylene with thickness over 5 mm to insulate the
connection part of pipe.
High pressure
pipe
Low pressure
pipe
When you insulate the pipe connection part, make sure
that overlapping part of the insulator is over 30 mm.
30 mm or
over
Insulator for pipe
connection part
Pipe insulation
Fix the pipe with a clamp and screws.
WARNING
• Cut the middle part of the pipe outlet protection rubber before
connecting the pipe.
Pipe outlet
protection
rubber
06 INSTALLATION