Cooling water management
2. Operation range of water
When the owrate of cooling water is out of the operation range, stop the outdoor unit and take care of the cause before
re-start the operation (Operation range : 60~120% of the standard the owrate of cooling water)
Section
Standard condition
Flowrate of cooling water (L/min)
AM080MXWA AM100MXWA AM120MXWA AM200MXWA AM300KXWA
Cooling
80 96 114 190 285
Heating
Section
Operation range
Flowrate of cooling water (L/min)
AM080MXWA AM100MXWA AM120MXWA AM200MXWA AM300KXWA
Cooling
48~96 58~115 68~137 114~228 170~342
Heating
80
70
60
50
40
30
20
10
0
50.00
100.0 150.0
Cooling Water Pressure Drop (kPa)
Flowrate of cooling water (L/min)
AM080MXWA
AM100MXWA
AM120MXWA
80
70
90
60
50
40
30
20
10
0
50 1000 150 200 250
Cooling Water Pressure Drop (kPa)
Flowrate of cooling water (L/min)
AM200MXWA
80
70
60
50
40
30
20
10
0
1000 200 300 400
Cooling Water Pressure Drop (kPa)
Flowrate of cooling water (L/min)
AM300KXWA