Things to check after completing the installation
Drain pipe work
• Have you checked if the drain pipes of the indoor and outdoor unit are
connected together?
• Have you completed the drain test?
• Is the drain pipe properly insulated?
Electrical wiring work
• Are the power cable and communication cable tightened rmly on the
terminal board within the range of rated tightening torque?
• Have you checked for cross-connection of the power and communication
cables?
• Have you performed the earthing work 3 to the outdoor unit?
• Did you make sure to use 2-core cable (not multi-core cable) for the
communication cable?
• Is the length of the wire within allowed range?
• Is the wiring route correct?
Setting address
• Did you set the address of the indoor and outdoor units properly?
• Did you set the address of the indoor and outdoor units properly? (When
using multiple remote controllers)
Option
• If there is a possibility of the outdoor unit from vibrating, check whether the
anti-vibration frame is correctly installed.
Inspection and test operation
Precautions before trial operation
• When the outdoor temperature is low, turn on the main power 6 hours before beginning the operation.
- If you start the operation immediately after turning on the main power, it may cause serious damage to the
part within the product.
• Do not touch the refrigerant pipe during or right after the operation.
- Refrigerant pipe may be hot or cold during or right after the operation depending on the status of the
refrigerant which ows through the refrigerant pipe, compressor and other parts of the refrigerant cycle. If you
touch the refrigerant during or right after the operation, you may get burns or frostbite.
• Do not operate the product with its panel or protection nets o.
- There is risk of personal injury from the parts that rotates, heated or with the high voltage.
• Do not cut o the main power right after stopping the operation.
- Wait for at least 5 minutes before turning o the main power. If not, water leakage or other problems may
occur.
• Connect all the indoor units and the power supply for the outdoor unit and run auto address setting. Run auto
address setting even after changing the indoor unit PCB.
CAUTION