ENGLISH-12
Space requirement for installation
Minimum space requirement for installation
Secure minimum installation space as shown in the following gures, considering service area and path for people etc.
- If the installation space is narrow, installer or other worker may get injured during work and may also cause problem to
the product.
If the conditions does not meet the space requirement in this manual, please contact qualied installation agent.
Single installation
When the water pipe passes through top of the product
(Unit : mm)
<Top view>
Service space
Front side
C
Space for installing water
pipe
20
Outdoor unit
350
A
100
B
300
<Front view>
Anti-vibration pad
1000 500100
When the water pipe passes through back of the product
(Unit : mm)
<Top view>
Service space
Front side
C
Space for installing water
pipe
300
Outdoor unit
350
A
300
B 500
<Front view>
Anti-vibration pad
1000 100100