ENGLISH-28
Capacity (kW)
Model
1 .5 1 .7 2 .2 2 .8 3 .2 3 .6 4 .5 5 .6 6 7 .1 8 .2 9 9.3 11 .2 12 .8 14 16 18 22 22 .4 28 32 50
500
CMH
1000
CMH
MSP duct
(with drain pump)
(AMKNMDE)
0 .24 0 .24 0 .24 0 .28 0 .28 0 .28 0 .32 0 .54 0 .68 0 .68 0 .91
Home Duct
(AMKNLDEH)
0.13 0.13 0.13 0.17
Ceiling
(AMFNCDE/
AMJNCDK)
0 .39 0 .39 0 .56 0 .95
Console
(AMNJDE)
0 .16 0 .27 0 .27 0 .27 0 .27
Neo forte
(AMFNTDE)
0 .24 0 .24 0 .24 0 .24 0 .36 0 .36
Neo forte (with EEV)
(AMFNQDE)
0 .34 0 .34 0 .34 0 .34 0 .51 0 .51 0 .51
AR5000
(AMJNADK)
0 .16 0 .16 0 .19 0 .25 0 .25 0 .52 0 .52 0 .52
AR5000 (with EEV)
(AMJNVDK)
0 .22 0 .22 0 .25 0 .34 0 .34 0 .71 0 .71 0 .71
New Boracay
(AMKNTDE)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
New Boracay
(with EEV)
(AMKNQDE)
0.24 0.24 0.32 0.32 0.49 0.49 0.49
MAX 4
(AMMNQDE)
0.49
HSP duct
(AMFNHDE)
0 .68 0 .68 0 .68 1 .18 1 .18
OAP duct
(AMJNEPE)
0 .68 1 .18 1 .18
Big duct
(AMJNHFK)
1 .15 1 .15
PAC
(AMJNPD)
0.73 1.85
Hydro Unit HE
(AMFNBD)
0.6 0.7 1.2
Hydro Unit HT
(AMFNBF)
0.6
note1)
MCU
(MCU-SNEN)
0.5
If AHU kit is included among the indoor units, you must add 0.063 kg of refrigerant for every 1 kW of the AHU capacity
increase.
Note1) In case the capacity conjunction of the Hydro Unit HT exceeds 50 % among the total indoor unit, please don’t put the
additional refrigerant.