01 BEFORE INSTALLATION
Outdoor unit combination
Make sure to use an indoor unit that is compatible with DVM S WATER-GEO.
Indoor units can be connected within the range indicated in following table.
If the total capacity of the connected indoor units exceeds the indicated maximum capacity, cooling and heating capacity
of the indoor unit may decrease.
Total capacity of the connected indoor units can be allowed from 50% to 130% of the total outdoor unit capacity. 0.5 ×
Σ(Outdoor unit capacity) ≤ Total capacity of the connected indoor units ≤ 1.3 × Σ(Outdoor unit capacity)
You can connect maximum 64 indoor units to the outdoor unit. Maximum quantity of connectable indoor unit is set to 64
since outdoor unit only support up to 64 communication address. Indoor unit address can be assigned from 0~63. If the
indoor unit address was assigned from 64~79, E201 error will occur.
Maximum 32 Wall-mount type indoor units with EEV (AMNQDEH, AMJNV) can be connected.
Do not install 1st-generation MCU and 2nd-generation MCU together.
- 1st-generation MCU: MCU-SNEEN
- 2nd-generation MCU: MCU-SNEK2N, MCU-S4NEK3N, MCU-S1NEK1N
• Use the following table to determine the size and number of outdoor units needed to achieve thecapacity
requirements.
CAUTION
Premium energy eciency type
Model name for combination
AM080MXWANR AM100MXWANR AM120MXWANR AM160MXWANR2 AM180MXWANR2 AM200MXWANR
Number of individual outdoor units
1 1 1 2 2 1
Combined outdoor unit
AM080MXWANR
1 2 1
AM100MXWANR
1 1
AM120MXWANR
1
AM200MXWANR
1
Rated capacity
Cooling (kW)
22.4 28.0 33.6 44.8 50.4 56.0
Heating (kW)
25.2 31.5 37.8 50.4 56.7 63.0
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
11.2 14.0 16.8 22.4 25.2 28.0
Maximum (kW)
29.1 36.4 43.7 58.2 65.5 72.8
Maximum number of connectable indoor
units
14 18 22 29 32 36
Model name for combination
AM220MXWANR2 AM240MXWANR2 AM260MXWANR2 AM280MXWANR2 AM300MXWANR2 AM320MXWANR2
Number of individual outdoor units
2 2 3 2 2 2
Combined outdoor unit
AM080MXWANR
2 1
AM100MXWANR
1 1 1
AM120MXWANR
1 2 1
AM200MXWANR
1 1 1
Rated capacity
Cooling (kW)
61.6 67.2 72.8 78.4 84.0 89.6
Heating (kW)
69.3 75.6 81.9 88.2 94.5 100.8
Total capacity of the
connected indoor units
(Cooling)
Minimum (kW)
30.8 33.6 36.4 39.2 42.0 44.8
Maximum (kW)
80.1 87.4 94.6 101.9 109.2 116.5
Maximum number of connectable indoor
units