02 INSTALLING THE PRODUCT
K2 (Number of press) KEY operation Display on segment
1 time Refrigerant charging in Cooling mode K - 5 - BLANK - BLANK
2 times Trial operation in Cooling mode K - 6 - BLANK - BLANK
3 times Pump down all units in Cooling mode K - 7 - BLANK - BLANK
4 times
HR: Pipe connection inspection
H/P: Auto trial operation
K - 8 - BLANK - BLANK
5 times Checking the amount of refrigerant
K - 9 - X - X
(Display of last two digits may dier depending on
the status)
6 times Discharge mode of DC link voltage K - A - BLANK - BLANK
7 times Forced oil collection K - C - BLANK - BLANK
8 times Inspect inverter compressor 1 K - D - BLANK - BLANK
9 times Inspect inverter compressor 2 K - E - BLANK - BLANK
10 times Water pipe valve/Pump check K - F - BLANK - BLANK
11 times Cooling fan/Flow control valve check K - G - BLANK - BLANK
12 times
A type PBA End key operation -
B type PBA
HR : Auto pipe pairing,
H/P : Unused
“K””H”XX
(Display of last two digits may dier
depending on the progress)
13 times B type PBA End key operation -
During “Discharge mode of DC link voltage,” voltage of INV1 and INV2 will be displayed alternately.
Even when the outdoor unit power is o, it is dangerous when you come in contact with inverter PCB and fan PCB since
they are charged with high DC voltage.
When pressing K2 key 9 to 12 times without inverter checker, error code can be displayed on segment even though the
outdoor unit is normal.
When replacing/repairing the PCB, cut o the power and wait until the DC voltage is discharged before replacing/
repairing them (Wait for more than 15 minutes to allow it to discharge naturally.)
When there were error, ‘Discharge mode of DC link voltage’ may not have been eective. Especially if error E464 and E364
have been occurred, power element might be damaged by re and therefore, do not use the ‘Discharge mode of DC link
voltage.’
If the 1st-generation MCU is installed, the Auto pipe pairing operation can not be used.
If the 2nd-generation MCU is installed, the Checking the pipe connection can not be used.
- 1st-generation MCU : MCU-S*NEE*N
- 2nd-generation MCU : MCU-S*NEK2N,MCU-S4NEK3N,MCU-S1NEK1N
If there is an A type PBA among the outdoor units installed as a module, the Auto pipe pairing operation can not be used.
K3 (Number of
press)
KEY operation Display on segment
1 time Intialize (Reset) setting Same as initial state
Setting outdoor unit option switch and key funtion