02 INSTALLING THE PRODUCT
Before running the Auto pipe pairing operation, be sure to close the front cabinet. If this operation is run with the front
cabinet open, the product may be damaged and the pipe addresses cannot be correctly recognized.
To run the Auto pipe pairing operation, take the following steps:
1. Press the K2 button 12 times on the B type main PBA of the outdoor unit to start the Auto pipe pairing operation.
(Display :
.)
Water temperature < 35
°C 30°C < Water temperature
Main heating operation Main cooling operation
Each step is indicated on the outdoor unit display. (The whole operation takes about 25 to 55minutes normally,
depending on the number of indoor units connected. However, it can be operated for up to 2 hours to protect the
compressor.)
- Step 1 (Start
) Steps 2 to 8 (Setup ) Step 9 (Check ) Step 10 (Con rmation )
2. When the Auto pipe pairing operation  nishes, the following data is shown on the outdoor unit display.
Result Outdoor unit display Description
Setting completed End
Setting error
E191
Indoor unit data
(displayed alternately)
Indoor unit data
- SEG 1,2 = indoor unit address / SEG 3,4 = error status
00: An MCU port is not disabled, or a
pipe is not connected.
01: Cooling only indoor unit is
connected to MCU.
02: The shared setting for two ports
is incorrect.
Example) When the MCU port connected to the indoor unit 12 is
disabled, E191 and 1200 are displayed alternately
- If two or more indoor units have setting errors, the data about the
next indoor unit is displayed each time you press the K2 switch.
• If the MCU ports to use are set incorrectly, the Auto pipe pairing operation may stop due to high-pressure or low-
pressure protection control or the data about the indoor unit that has a MCU port setting error may be incorrect. Ensure
that the MCU ports to use are set correctly.
• Depending on the indoor and water temperature, the Auto pipe pairing operation may stop due to protection control.
• If an error occurs while the Auto pipe pairing operation is running, check the error code and take actions.
• If you cannot  nish the Auto pipe pairing operation because of the previous reasons, set the pipe addresses manually by
referring to Setting the Pipe Addresses Manually.