ENGLISH-91
02 INSTALLING THE PRODUCT
Wiring method for optional functions
Installation example of AC 220-240 V, direct operation type 2way solenoid valve
PUMP/2Way solenoid valve controller (PBA)
Controller
Outdoor unit
2Way solenoid valve
Flow switch
AC 220-240 V
AC 220-240 V
2Way solenoid valve
OUT
PUMP OUT
PUMP F/B IN
Relay
Relay
Caution for wiring
Internal part of outdoor unit External part of outdoor unit
2way solenoid valve is a type that works at AC 220-240 V 50/60 Hz and supports product with 0.2 A or low.
- For 2way solenoid valve with over 0.2 A, connect external power.
- For external power cable for 2way solenoid valve must use 600 V ame-resisting double layered cable.
Product will not operate when ow switch is not installed.
Installation example of extra controller such as 2way solenoid valve and pump etc.
PUMP/2Way solenoid valve controller (PBA)
Controller
Outdoor unit
2Way
solenoid
valve
Flow switch
AC 220-240 V
AC 220-240 V
2Way solenoid
valve OUT
PUMP OUT
PUMP F/B IN
Relay
Relay
Caution for
wiring
PUMP
AC 220-
240 V
2Way solenoid valve, Pump controller
2Way solenoid
valve, Pump
controller
Internal part of outdoor unit External part of outdoor unit
FUSE
If the operation type of 2way solenoid valve is dierent, use extra controller.
- Also use external controller for pump.
- Outdoor unit only provides contact signal needed for 2way solenoid valve and pump operation. Therefore, do not use
the contact signal from the air conditioner directly.
Product will not operate when ow switch is not installed.