Product Specifications
Samsung Electronics 30
Indoor Unit (cont.)
Ŷ Big Ceiling
Model AM112JNCDKH/EU AM140JNCDKH/EU
Power Supply φ,V,Hz 1,220~240,50/60 1,220~240,50/60
Mode
1) -
HP / HR HP / HR
Performance Capacity
Cooling
2)
kW 11.2 14.0
Heating
3)
kW 12.5 16.0
Power
Input Consumption (Cooling/Heating) W 92/80 160/160
Running Current (Cooling/Heating) A 0.94/0.83 1.45/1.45
Indoorunit refrigerant adding amount Kg/EA 0.56 0.95
Noise Level Actual Noise Pressure (High) dB(A) ײ 49 52
Fan
Type - Sirocco, Φ168*3EA Sirocco, Φ168*4EA
Motor
Model -
SIC-70CW-F1153-6,
DL-12830SSBF
(DB31-00660A)
SIC-80CW-F1244-2,
DL-12830SSBK
(DB31-00661A)
Type - BLDC Feedback BLDC Feedback
Output W 153W 244W
Airflow Rate Fan(H/M/L)
᎑/min
29.3/23.9/18.5 36.4/30.8/26.0
Refrigerant
Type - R410a R410a
Control Method - EDM EEV 4.0C EDM EEV 4.0C
Temperature Control - Micom&Thermistors Micom&Thermistors
Safety Devices - 250V/5A 250V/5A
Piping
Connections
Liquid (Flare)
Φ,mm 9.52 9.52
Φinch 3/8 3/8
Gas (Flare)
Φ,mm 15.88 15.88
Φinch 5/8 5/8
Drain
Φ,mm VP25 (OD25,ID 20) VP25 (OD25,ID 20)
Φinch - -
Weight
Net Weight kg 33.5 42.5
Shipping Weight kg 39.5 48.5
Dimensions
Net Dimensions (W×H×D)
mm 1350*235*675 1650*235*675
inch - -
Shipping Dimensions (W×H×D)
mm 1439*758*321 1739*758*321
inch - -
Functions
Auto Restart - O O
Auto Swing - O O
Group/Individual Control - O O
External Contact Control - O O
Trouble Shooting by LED - O O
Standard
Accessories
Installation Manual - O O
Operation Manual - O O
Pattern Sheet for Installation - O O
Flexible Drain Hose - O O
Filter / Safety Grille - Filter (Washable) Filter (Washable)
Optional
Accessories
Wireless Remote Controller - AR-DH00 AR-DH00
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N
External Contact Interface Module - MIM-B14 MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Norminal cooling capacities are based on;
- Indoor temperature : 27ఁ DB, 19ఁ WB - Outdoor temperature : 35ఁ DB, 24ఁ WB
*3) Norminal heating capacities are based on;
- Indoor temperature : 20ఁ DB, 15ఁ WB - Outdoor temperature : 7ఁ DB, 6ఁ WB
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.
*5) Specifications may be subject to change without prior notice for product improvement.