Product Specifications
Samsung Electronics 49
Indoor Unit (cont.)
Ŷ Hydro Unit
1) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Rated flow standard : Temperature of the Outlet water 18
2) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Rated flow standard : Temperature of the Outlet water 35
3) Rated heating capacity : Outdoor temperature 7˚C standard and outdoor temperature falls below zero, heating capacity can drop, depending
on the temperature condition.
4) Equivalent refrigerant piping : 7.5m, Level differences : 0m
Typ e
(Hydro Unit)
Model AM160FNBDEH/EU AM320FNBDEH/EU AM500FNBDEH/EU
Division Cooling/Heating Cooling/Heating Cooling/Heating
Power Supply 1ø, 220-240V, 50Hz , 220-240V, 50Hz 1ø, 220-240V, 50Hz
Performance
Horse Power HP 5 10 16
Cooling
kW 14.0 28.0 44.8
Kcal/h 12040 24080 38528
Heating
kW 16.0 31.5 50.4
Kcal/h 13760 27090 43344
Power
Running Current A 0.05 0.05 0.05
Input W 10 10 10
Piping
(Refrigerant)
Liquid ø,mm 9.52 9.52 12.7
Gas ø,mm 15.9 22.2 28.58
Piping
(Water)
Inlet/Outlet A(Inch) 25A(PT1) 25A(PT1) 32A(PT 1-1/4)
Max. Hydraulic Mpa 1.0 1.0 1.0
Rated flow rate(Water Piping) LPM 48 92 150
Set Size
Net Weight kg 29 33 40
Shipping Weight kg 31 35 42
Net Dimension(WxHxD) mm 518X627X330 518X627X330 518X627X330
Shippingt Dimension(WxHxD) mm 652X700X426 652X700X426 652X700X426