68 Samsung Electronics
Indoor Unit (cont.)
Ŷ EHS TDM PLUS -Wall Monuted type(cont.)
Model AE056MNADEH/EU AE071MNADEH/EU
Power Supply Φ,#,V,Hz
1,220~240,50 1,220~240,50
Mode *
HP / HR HP / HR
Performance Capacity
Cooling*
kW
5.6 7.1
Btu/h
19,096 24,211
Heating*
kW
6.3 8.0
Btu/h
21,483 27,280
Power
Power Input
Cooling W
27 41
Heating W
37 53
Current Input
Cooling A
0.21 0.31
Heating A
0.29 0.41
Fan
Motor
Type -
Crossflow Fan 106*L830 Crossflow Fan 106*L830
Output W
27 27
Number of unit
11
Airflow Rate
Cooling(High)
᎑/mim
11.80 14.80
Heating(High)
᎑/mim
15.00 18.00
Piping
Connections
Liquid Pipe
Φ,᎖
6.35 9.52
Φ,inch
1/4כ 3/8כ
Gas Pipe
Φ,᎖
12.70 15.88
Φ,inch
1/2כ 5/8כ
Drain Pipe Φ,᎖
ID 18 HOSE ID 18 HOSE
Field Wiring
Power Source
Wire
Below 20m/
over 20m
mm2
1.5 ~ 2.5 1.5 ~ 2.5
Transmission Cable mm2
0.75 ~ 1.50 0.75 ~ 1.50
Refrigerant
Type -
R410A R410A
Control Method -
EEV INCLUDED EEV INCLUDED
Sound
Sound
Pressure*
High/Mid/Low dBA
39/36/33 44/41/36
Dimensions
Net Weight
Ꭰ
14.6 14.6
Shipping Weight
Ꭰ
17.0 17.0
Net Dimensions (W x Hx D)
᎖
1063*317*294 1063*317*294
Shipping Dimensions (W x Hx D)
᎖
1123*384*354 1123*384*354
Functions
Auto Restart - O O
Auto Swing - O O
Group/Individual Control - O O
External Contact Control - O O
Trouble Shooting by LED - O O
Standard
Accessories
Installation Manual - O O
Operation Manual - O O
Pattern Sheet for Installation - X X
Flexible Drain Hose - O O
Filter / Safety Grille - Filter (Washable) Filter (Washable)
Wireless Remote Controller MR-EH00 MR-EH00
Optional
Accessories
Wireless Remote Controller - - -
Wired Remote
Controller
Simplified - MWR-WE10N MWR-WE10N
External Contact Interface Module - MIM-B14 MIM-B14
*1) Mode
- HP : Heat Pump, HR : Heat Recovery
*2) Nominal cooling capacities are based on;
- Indoor temperature : 27˚C DB, 19˚C WB
- Outdoor temperature : 35˚C DB, 24˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*3) Nominal heating capacities are based on;
- Indoor temperature : 20˚C DB, 15˚C WB
- Outdoor temperature : 7˚C DB, 6˚C WB, Equivalent refrigerant piping : 7.5m, Level differences : 0m
*4) Sound pressure was acquired in a dead room. Thus actual noise level may be different depending on the installation conditions.