Troubleshooting
4-102 Samsung Electronics
1.
Cause of problem
4-4-58 3-phase Input Wiring error
Outdoor unit display
Indoorunit display
×(Operation) (Reservation) (Blast) (Filter) ×(Defrost)
Judgment Method
. When turn on the power and check the status of the power from the inverter .
If the phase does not connect the power(no phase) : E425 or E466 (E366) is displayed (Air conditioner to maintain
the normal state.)
However) N-phase must be pr operly connected.
Cause of problem
 Check the input wiring
 EMI Fuse short
Replace Inverter PCB
Power Off
Yes
Yes
No
Yes
Did the Main
Terminal Block and Power R, S, T, N is
connected properly?
Power BOX Terminal : Check the phase-to-phase
connection 380V of the R, S, T and then restart.
(N-phase must be properly connected.)
No
No
No
Yes
Connection and then restart it
Low voltage error during this initial charge :
Replace Fuse, if the rectifier diode of the inverter
PCB is normal.
Connection and then restart it
Did the Reactor
C
onnection Terminal is connected
properly?
Did the EMI PCB Fuse is short?
Is EMI PCB CN21
connector and Inverter PCB accurately
connected?

Table of Contents

Other manuals for Samsung AM160FNBFGB/EU

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Samsung AM160FNBFGB/EU and is the answer not in the manual?

Samsung AM160FNBFGB/EU Specifications

General IconGeneral
ModelAM160FNBFGB/EU
TypeHeat Pump
Cooling Capacity16.0 kW
Heating Capacity18.0 kW
Energy Efficiency Class (Cooling)A++
Energy Efficiency Class (Heating)A+
RefrigerantR410A
Operating Temperature Range (Heating)-20°C to 24°C
Power Supply50Hz
Dimensions (Outdoor Unit)940 x 330 mm

Related product manuals