EasyManua.ls Logo

Samsung MH035FPEA - Outdoor Unit Accessories

Samsung MH035FPEA
158 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MH052FPEA
The indoor unit is powered from the outdoor unit via the connection cord.
1. Remove the screw on the electrical component box and remove the cover plate.
2.
Route the connection cord through the side of the indoor unit and connect the cable to terminals; refer to the figure below.
3.
Route the other end of the cable to the outdoor unit through the ceiling & the hole on the wall.
4.
Reassemble the electrical component box cover, carefully tightening the screw.
Between Indoor and Outdoor Connection Cord Specifications
Operation Instruction & Installation
31Samsung Electronics
220-240V~
/50Hz
±10%
2.0mm
2
(H07RN-F, 3G)
ø1.6mm
(2 wires)
0.75~
1.25mm
2
(H07RN-F,
2 wires)
0.75~
1.25mm
2
(2 wires)
Power Supply (Single Phase)
Power Supply Max/Min(V)
Connection Wire
Earth Cable
Communication
Cable
Home
server
Keep the power cable and the connection cord in a steel pipe to protect them against liquids, outside
impacts and so on.
DB98_20402A(1)_1 10/26/04 2:48 PM Page 31