E-136
Contact Control Pattern Selection
1
Click [System Settings]
£
[System environment setting]
when DMS2.5 web page menu screen appears.
2
Click [Edit] from contact point pattern selection window.
3
Select the pattern you want to check.
X
Pattern 1[No external input]:
No operation will be made when inputting contact control
s
ignal.
X
Pattern 2[Level(Emergency stop)]:
Commands that stop all operation of indoor unit and
d
isable remote control when inputting contact control
signal. In level emergency stop status, it will not be
controlled even if the command is from upper controller.
X
Pattern 3[Level(Operation/Stop)]:
Level signal input timing.
It changes operation/stop status of all indoor units.
X
Pattern 4[pulse (Operation/Stop,Disable/Enable)]:
Pulse signal. It changes operation/stop status of all indoor
u
nits.
4
Click [Save] after setting is completed.
3
1
2
4
System Settings (Continued)