E-152
System Settings (Continued)
6
Tracking completed message will appear.
Select Zone initialization mode you want and click [OK].
X
Not initialize: No zone information initialization will be
made.
X
Initialize individually: Initialize zone information as
individual mode.
X
Initialize by group: Initialize zone information as group
mode.
Note
XIf tracking is executed successfully while NEW is set
as communication mode for each channel, virtual
OnOffcontroller will be assigned to each channel.
XIf there is no searched outdoor unit, OnOff controller,
SIM/PIM, it is regarded as DVM tracking failure.
XIf there are devices which have same address, first
searched device will be registered only.
XThe number of OnOff controller doesn't contain
the number of virtual OnOff controller that is used
in NEW communication.
XGroup initialization will not be applied to Hydro Unit,
Hydro Unit HT and Single EHS.
XIf you execute tracking, system setting will be initialized.
XIf tracking result does not match with actual installation
information, there can be critical error in additional
functions such as power distribution.
X
Make sure that tracking information matches to actual
installation information after tracking.
6