3. Electric Characteristics
NOTE
MCA : Minimum circuit amperes
MFA : Maximum fuse amperes
FLA : Full load amperes
Essential
HP kW Hz Voltage
Min.
(-10%)
Max.
(+10%)
Cooling Heating MCA MFA kW FLA [A]
10 28.0 AM100AXVDGH/EU 50 380-415 342 456 20.50 14.34 23.0 32 0.63 7.3
12 33.6 AM120AXVDGH/EU 50 380-415 342 456 22.01 16.45 25.0 32 0.63 7.3
14 40.0 AM140AXVDGH/EU 50 380-415 342 456 28.60 20.91 29.0 32 0.63 7.3
16 45.0 AM160AXVDGH/EU 50 380-415 342 456 31.04 22.38 32.0 40 1.24 14.6
18 50.4 AM180AXVDGH/EU 50 380-415 342 456 37.61 24.75 39.2 50 1.24 14.6
20 56.0 AM200AXVDGH1EU 50 380-415 342 456 41.00 28.68 46.0 63 1.26 14.6
22 61.6 AM220AXVDGH1EU 50 380-415 342 456 42.51 30.79 48.0 63 1.26 14.6
24 68.0 AM240AXVDGH1EU 50 380-415 342 456 49.10 35.25 52.0 63 1.26 14.6
26 73.0 AM260AXVDGH1EU 50 380-415 342 456 51.54 36.72 55.0 63 1.87 21.9
28 78.6 AM280AXVDGH1EU 50 380-415 342 456 53.05 38.83 57.0 63 1.87 21.9
30 84.0 AM300AXVDGH1EU 50 380-415 342 456 59.62 41.20 64.2 75 1.87 21.9
32 90.0 AM320AXVDGH1EU 50 380-415 342 456 62.08 44.76 64.0 75 2.48 29.2
34 95.4 AM340AXVDGH1EU 50 380-415 342 456 68.65 47.13 71.2 80 2.48 29.2
36 100.8 AM360AXVDGH1EU 50 380-415 342 456 75.22 49.50 78.4 90 2.48 29.2
38 106.6 AM380AXVDGH1EU 50 380-415 342 456 73.55 53.17 80.0 90 2.50 29.2
40 112.0 AM400AXVDGH1EU 50 380-415 342 456 80.12 55.54 87.2 100 2.50 29.2
Current [A] ODU Fan MotorCapacity
Model Name
Power Supply Voltage Range Running Current [A]