11
5. Failure code table
Failure
code
Description
Alarm
phenomenon
Alarm action
Elimination
method
E00
Communication
failure alarm
E00 shown with
alarm sound
None
Automatic clearing
after mainboard
and operation panel
are connected well
E01
flow alarm
E01 shown with
alarm sound
The compressor, condenser fans and
heater shut down
Automatic clearing
E02
Ultra-high room
temp.alarm
E02 shown with
alarm sound
Each refrigeration part runs under
usual procedures
Automatic clearing
E03
ultra-low water temp
alarm
E03 shown with
alarm sound
The compressor, condenser fans and
heater shut down
Automatic clearing
E04
ultra-low water temp
alarm
E04 shown with
alarm sound
Each refrigeration part runs under
usual procedures
Automatic clearing
E05
Wrong phase and
lacking phase alarm
E05 shown with
alarm sound
The water pump, compressor,
condenser fans and heater shut down
Manual clearing
E06
Compressor overload
alarm
E06 shown with
alarm sound
The compressor, condenser fans and
heater shut down
Manual clearing
E07
water pump overload
alarm
E07 shown with
alarm sound
The water pump, compressor,
condenser fans and heater shut down
Manual clearing
E08
Refrigeration system
high pressure alarm
E08 shown with
alarm sound
The compressor and condenser fans
shut down
Manual clearing
E09
Refrigeration system
low pressure alarm
E09 shown with
alarm sound
The compressor and condenser fans
shut down
Automatic clearing
E10
Room temp. sensor
failure alarm
E10 shown with
alarm sound
Switched to constant temp. mode and
each refrigeration part runs under
usual procedures
Automatic clearing
E11
water temp. sensor
failure alarm
E11 shown with
alarm sound
The water compressor, condenser
fans and heater shut down
Automatic clearing
E12
Ultra-low water level
alarm
E12 shown with
alarm sound
The unit runs normally under set
values; the water pump, compressor,
condenser fans and heater shut down
Automatic clearing
E13
Exhaust temp. sensor
failure alarm
E13 shown with
alarm sound
Each refrigeration part runs under
usual procedures
Automatic clearing
E14
Ultra-high exhaust
temp. alarm
E14 shown with
alarm sound
Each refrigeration part runs under
usual procedures
Automatic clearing