CWFL-3000/4000/6000 Series
0x0802
Alarm status
high 16-bit
MSByte
Bit7(MSb)
Retain
Bit6
Retain
Bit5
Retain
Bit4
Retain
Bit3
Retain
Bit2
Retain
Bit1
Retain
Bit0(LSb)
Retain
LSByte
Bit7(MSb)
Write administrator
parameter error
0Correct 1Error
Bit6 Write user parameter error 0Correct 1Error
Bit5
Ultra-high exhaust temp.
alarm
0No alarm 1Alarm
Bit4
Exhaust temp. sensor failure
alarm
0No alarm 1Alarm
Bit3 Ultra-low water temp alarm 0No alarm 1Alarm
Bit2 Ultra-low conductivity alarm 0No alarm 1Alarm
Bit1 Ultra-high conductivity alarm 0No alarm 1Alarm
Bit0(LSb)
High temp. system water
temp. sensor failure alarm
0No alarm 1Alarm
0x0803
Alarm status
low 16-bit
MSByte
Bit7(MSb)
Low temp. system water
temp. sensor failure
0No alarm 1Alarm
Bit6 Room temp. sensor failure 0No alarm 1Alarm
Bit5
Refrigeration system low
pressure
0No alarm 1Alarm
Bit4
Refrigeration system High
pressure
0No alarm 1Alarm
Bit3
High temp. water pump
overload
0No alarm 1Alarm
Bit2
Low temp. water pump
overload
0No alarm 1Alarm
Bit1
Compressor overload
0No alarm 1Alarm
Bit0(LSb)
Wrong phase and lacking
phase
0No alarm 1Alarm
LSByte Bit7(MSb)
High temp. system ultra-high
water temp
0No alarm 1Alarm
5. Read/Write Registers(Use only when the external input
function is turned off)
Register address Description Range Default Unit Remark Symbol
0x0804 Chiller On/Off 0-1 -- 0On1Off No